2013-09-18 13:56:59 | 2010 FBC / MASTER MODEL "E" |
| |
| DENIED BY BUILDING |
| |
| 1) SHEETS A0.1,1.2, 2.1,3.1A,3.1B,4.1,AND 5.1 ARE |
| MISSING FROM THE PLAN SETS THAT WERE SUBMITTED. CITY |
| AMENDMENTS 107.2.1 |
| |
| 2) THE PLANS ARE NOT IN THE ORDER SPECIFIED BY THE |
| DRAWING INDEX ON THE COVER SHEET. CITY AMENDMENTS |
| 107.2.1 |
| |
| 3) SUBMIT TWO SETS OF MODEL "E" WORSE CASE ENERGY |
| CALCULATIONS AND EQUIPMENT SIZING CALCULATIONS FOR THE |
| MASTER PER 2010 FBC ENERGY CONSERVATION. SITE SPECIFIC |
| ENERGY CALCULATIONS WILL BE REQUIRED FOR EACH PERMIT |
| APPLIED FOR UNDER THE MASTER. |
| |
| 4) SUBMIT TWO COPIES OF A GENERIC MODEL "E" SITE PLANS |
| THAT INCLUDE SURFACE WATER DRAINAGE FOR THE MASTER. |
| SITE SPECIFIC SITE PLANS WITH DRAINAGE SHOWN AND |
| SURVEYS WILL BE REQUIRED FOR EACH PERMIT APPLIED FOR |
| UNDER THE MASTER. FBC R401.3 |
| |
| 5) ON SHEET S-2 THE ALLOWABLE COMPONENT AND CLADDING |
| WIND PRESSURES FOR THE WALL ZONES IN THE TABLE HAVE AN |
| AREA OF 25 SQFT. THE PRESSURES SPECIFIED ON SHEET S-1 |
| ARE INCORRECTLY SPECIFYING THESE PRESSURES FOR OPENINGS |
| THAT ARE LESS THAN 25 SQFT. FOR WORSE CASE, SPECIFY THE |
| PRESSURES FOR A 10 SQFT AREA IN THE TABLE AND FOR THE |
| SMALLER OPENINGS. FBC R301.2.1 |
| |
| 6) ON SHEET S-2, UNDER CONCRETE NOTE #3, THE 1994 |
| EDITION OF ACI 315 IS SPECIFIED. PLEASE CHANGE TO 2008 |
| EDITION WHICH IS THE EDITION REFERENCED BY THE 2010 |
| FBCR OR JUST CURRENT EDITION. FBCR CHAPTER 43 |
| |
| 7) SUBMIT TWO SETS OF TRUSS DRAWINGS AND LAYOUTS FOR |
| ASCE7-10, 170 MPH AND EXPOSURE C THAT HAVE BEEN SIGNED |
| AND SEALED BY THE TRUSS ENGINEER AND REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE |
| MODEL "E" STRUCTURE. FBC R802.1.6.1 THESE ARE REQUIRED |
| TO BE SUBMITTED AND REVIEWED FOR THE MASTER. |
| |
| 8) TWO COPIES OF PRODUCT APPROVALS ARE REQUIRED FOR |
| EACH TYPE OF WINDOW AND DOOR, STRUCTURAL MULLIONS, ROOF |
| COVERING, STORM PANELS (IF IMPACT GLAZING IS NOT USED), |
| BLOCK LINTELS, MANUFACTURED SIDING (IE HARDI-BOARD), |
| STRUCTURAL CONNECTORS (IE TRUSS ANCHORS) AS REQUIRED BY |
| DCA RULE 9N-3. NOTE:THE COPIED PRODUCT APPROVALS FROM |
| MODEL B THAT WERE SUBMITTED ARE CURRENT & CAN BE USED |
| IF THESE ARE THE PRODUCTS THAT WILL BE INSTALLED FOR |
| THIS MODEL. |
| |
| 9) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| AMENDMENTS 107.3.4.1 |
| |
| SEE REVIEW COMMENTS UNDER OTHER TRADES. |
| |