Plan Review Notes
Plan Review Notes For Permit 12120699
Permit Number 12120699
Review Stop B
Sequence Number 2
Notes
Date Text
2013-09-18 13:56:592010 FBC / MASTER MODEL "E"
  
 DENIED BY BUILDING
  
 1) SHEETS A0.1,1.2, 2.1,3.1A,3.1B,4.1,AND 5.1 ARE
 MISSING FROM THE PLAN SETS THAT WERE SUBMITTED. CITY
 AMENDMENTS 107.2.1
  
 2) THE PLANS ARE NOT IN THE ORDER SPECIFIED BY THE
 DRAWING INDEX ON THE COVER SHEET. CITY AMENDMENTS
 107.2.1
  
 3) SUBMIT TWO SETS OF MODEL "E" WORSE CASE ENERGY
 CALCULATIONS AND EQUIPMENT SIZING CALCULATIONS FOR THE
 MASTER PER 2010 FBC ENERGY CONSERVATION. SITE SPECIFIC
 ENERGY CALCULATIONS WILL BE REQUIRED FOR EACH PERMIT
 APPLIED FOR UNDER THE MASTER.
  
 4) SUBMIT TWO COPIES OF A GENERIC MODEL "E" SITE PLANS
 THAT INCLUDE SURFACE WATER DRAINAGE FOR THE MASTER.
 SITE SPECIFIC SITE PLANS WITH DRAINAGE SHOWN AND
 SURVEYS WILL BE REQUIRED FOR EACH PERMIT APPLIED FOR
 UNDER THE MASTER. FBC R401.3
  
 5) ON SHEET S-2 THE ALLOWABLE COMPONENT AND CLADDING
 WIND PRESSURES FOR THE WALL ZONES IN THE TABLE HAVE AN
 AREA OF 25 SQFT. THE PRESSURES SPECIFIED ON SHEET S-1
 ARE INCORRECTLY SPECIFYING THESE PRESSURES FOR OPENINGS
 THAT ARE LESS THAN 25 SQFT. FOR WORSE CASE, SPECIFY THE
 PRESSURES FOR A 10 SQFT AREA IN THE TABLE AND FOR THE
 SMALLER OPENINGS. FBC R301.2.1
  
 6) ON SHEET S-2, UNDER CONCRETE NOTE #3, THE 1994
 EDITION OF ACI 315 IS SPECIFIED. PLEASE CHANGE TO 2008
 EDITION WHICH IS THE EDITION REFERENCED BY THE 2010
 FBCR OR JUST CURRENT EDITION. FBCR CHAPTER 43
  
 7) SUBMIT TWO SETS OF TRUSS DRAWINGS AND LAYOUTS FOR
 ASCE7-10, 170 MPH AND EXPOSURE C THAT HAVE BEEN SIGNED
 AND SEALED BY THE TRUSS ENGINEER AND REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE
 MODEL "E" STRUCTURE. FBC R802.1.6.1 THESE ARE REQUIRED
 TO BE SUBMITTED AND REVIEWED FOR THE MASTER.
  
 8) TWO COPIES OF PRODUCT APPROVALS ARE REQUIRED FOR
 EACH TYPE OF WINDOW AND DOOR, STRUCTURAL MULLIONS, ROOF
 COVERING, STORM PANELS (IF IMPACT GLAZING IS NOT USED),
 BLOCK LINTELS, MANUFACTURED SIDING (IE HARDI-BOARD),
 STRUCTURAL CONNECTORS (IE TRUSS ANCHORS) AS REQUIRED BY
 DCA RULE 9N-3. NOTE:THE COPIED PRODUCT APPROVALS FROM
 MODEL B THAT WERE SUBMITTED ARE CURRENT & CAN BE USED
 IF THESE ARE THE PRODUCTS THAT WILL BE INSTALLED FOR
 THIS MODEL.
  
 9) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 SEE REVIEW COMMENTS UNDER OTHER TRADES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]