Plan Review Notes For Permit 12120699 |
Permit Number |
12120699 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-01-03 09:52:27 | 2010 FBC | | | | DENIED BY PLUMBING | | | | 1) TWO OR MORE SETS OF PLANS THAT HAVE BEEN SIGNED AND | | SEALED BY THE DESIGNER OF RECORD ARE REQUIRED TO BE | | SUBMITTED FOR PERMIT PER CITY AMENDMENTS 107.1. | | | | 2) REVISE PLUMBING NOTE #1 ON SHEET P-2 TO REFERENCE | | THE 2010 FBC. | | | | 3) REVISE THE AIR ADMITTANCE VALVE DETAIL TO REFERENCE | | THE CURRENT CODE SECTIONS (IE FBC PLUMBING 917.4 AND | | FBCR P3114.4). | | | | NOTE: THE ONE SET OF PLANS THAT WAS SUBMITTED WAS | | RED-LINED TO SHOW WHERE CORRECTIONS WERE NEEDED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|