Plan Review Notes For Permit 12120699 |
Permit Number |
12120699 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-01-03 11:27:42 | 2010 FBC | | | | DENIED BY MECHANICAL | | | | 1) TWO OR MORE SETS OF PLANS THAT HAVE BEEN SIGNED AND | | SEALED BY THE DESIGNER OF RECORD ARE REQUIRED TO BE | | SUBMITTED FOR PERMIT PER CITY AMENDMENTS 107.1. | | | | 2) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS AS | | REQUIRED BY FBCR M1401.3. | | | | 3) SUBMIT TWO SETS OF ENERGY CALCULATIONS AS REQUIRED | | BY FBC ENERGY CONSERVATION SECTION 405.4. | | | | 4) ON SHEET M-1 UPDATE THE WIND SPEED TO 170 MPH | | VULT/132 MPH VASD AND THE EDITION OF ASCE 7 TO ASCE | | 7-10. FBCR 301.2.1 AND CHAPTER 43. | | | | NOTE: THE ONE SET OF PLANS THAT WAS SUBMITTED WAS | | RED-LINED TO SHOW WHERE CORRECTIONS WERE NEEDED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|