Notes |
Date |
Text |
2013-01-03 09:56:10 | 2010 FBC | | | | DENIED BY ELECTRIC | | | | 1) ARC-FAULT CIRCUIT-INTERRUPTERS REQUIRED IN | | ACCORDANCE WITH 2008 NEC ARTICLE 210.12. | | | | 2) TAMPER-RESISTANT RECEPTACLES REQUIRED IN ACCORDANCE | | WITH 2008 NEC ARTICLE 210.12. | | | | 3) PLEASE UPDATE THE CODE EDITIONS REFERENCED ON | | ELECTRICAL SHEETS TO 2010 FBC, 2007 NFPA 72, 2009 NFPA | | 101 AND 2010 NFPA 1. | | | | 4) TWO OR MORE SETS OF PLANS THAT HAVE BEEN SIGNED AND | | SEALED BY THE DESIGNER OF RECORD ARE REQUIRED TO BE | | SUBMITTED FOR PERMIT PER CITY AMENDMENTS 107.1. | | | | NOTE: THE ONE SET OF PLANS THAT WAS SUBMITTED WAS | | REDLINED TO SHOW WHERE CORRECTIONS WERE NEEDED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|