2013-01-04 16:42:43 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) TWO OR MORE SETS OF PLANS THAT HAVE BEEN SIGNED AND |
| SEALED BY THE DESIGNER OF RECORD ARE REQUIRED TO BE |
| SUBMITTED FOR PERMIT PER CITY AMENDMENTS 107.1. |
| |
| 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS AS REQUIRED |
| BY FBC ENERGY CONSERVATION SECTION 405.4. |
| |
| 3) UPDATE THE WIND SPEED INFORMATION ON SHEET S-2 TO |
| 170 MPH VULT / 132 VASD. FBCR301.2.1 |
| |
| 4) UPDATE THE CODE AND STANDARDS REFERENCED ON SHEET |
| S-2 TO FBC 2010, ACI 318 - 2008, ACI 530 - 2008 AND ACI |
| 315 - 2008. FBCR CHAPTER 43 |
| |
| 5) EXPOSURE CATEGORY C IS SPECIFIED ON THE PLANS. NOTE: |
| IF THERE ARE ANY STRUCTURES THAT WILL BE CONSTRUCTED |
| UNDER THIS MASTER WITHIN 600 FT OF THE INTER-COASTAL |
| WATERWAY OR OTHER BODY OF WATER WITH A ONE MILE FETCH |
| THEN THEY ARE CONSIDERED EXPOSURE D. FBCR 301.2.1.4.2 |
| |
| 6) SUBMIT TWO COPIES OF A SURFACE DRAINAGE PLAN. |
| FBCR401.3 |
| |
| 7) UPDATE CODE AND STANDARDS ON THE COVER SHEET (IE |
| 2010 FBC, 2010 FIRE PREVENTION CODE,2008 NEC). NOTE: |
| THE FAIRHOUSING GUIDELINES DO NOT APPLY TO ONE AND TWO |
| FAMILY DWELLINGS. |
| |
| 8) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR EXTERIOR |
| WINDOWS, DOORS, ROOFING MATERIAL, BLOCK LINTELS, TRUSS |
| ANCHORS, ETC. AS REQUIRED BY DCA RULE 9N-3. |
| |
| 9) PRODUCT APPROVALS ARE REQUIRED TO REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PER CITY |
| AMENDMENTS 107.3.4.1. |
| |
| NOTE: THE ONE SET OF PLANS THAT WAS SUBMITTED WAS |
| RED-LINED TO SHOW WHERE CORRECTIONS WERE NEEDED. |
| |