Plan Review Notes
Plan Review Notes For Permit 12120697
Permit Number 12120697
Review Stop B
Sequence Number 5
Notes
Date Text
2014-06-30 13:02:482010 FBC
  
 TRUSS DRAWINGS ARE DENIED
  
 1) THE TRUSS LAYOUT AND DRAWINGS FOR THE MODEL 'A'
 GABLE OPTION DO NOT HAVE THE DESIGNER OF RECORD FOR THE
 STRUCTURE'S SHOP DRAWING REVIEW STAMP ON THEM. THEY
 NEED TO BE REVIEWED BY THE D.O.R. THE TRUSS LAYOUT
 APPEARS TO BE CONSISTENT WITH THE STRUCTURAL PLANS.
  
 2) THE TRUSS LAYOUT AND DRAWINGS FOR THE MODEL 'A' HIP
 OPTION DO NOT HAVE THE DESIGNER OF RECORD FOR THE
 STRUCTURE'S SHOP DRAWING REVIEW STAMP ON THEM. THEY
 NEED TO BE REVIEWED BY THE D.O.R. THE TRUSS LAYOUT
 APPEARS TO BE CONSISTENT WITH THE STRUCTURAL PLANS.
  
 3) THE TRUSS LAYOUTS FOR BOTH OPTIONS HAVE NOT BEEN
 SIGNED AND SEALED BY THE TRUSS ENGINEER. FS 471 & FAC
 61G15-31.003
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]