2013-09-17 18:43:17 | 2008 NEC | | | | DENIED BY ELECTRIC | | | | 1) THE MECHANICAL EQUIPMENT SCHEDULE SPECIFIES THE | | MAXIMUM OVER CURRENT PROTECTION FOR THE CONDENSING UNIT | | TO BE 30 AMPS. THE ELECTRICAL PANEL SCHEDULE SHOWS A 40 | | AMP BREAKER. PLEASE CORRECT. | | | | 2) PROVIDE A 2ND GROUND ROD TO MEET REQUIRED OHM | | RESISTANCE. NEC 250.56 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|