Plan Review Notes
Plan Review Notes For Permit 12120697
Permit Number 12120697
Review Stop B
Sequence Number 2
Notes
Date Text
2013-09-17 18:43:592010 FBC / MASTER MODEL "A"
  
 DENIED BY BUILDING
  
 1) SHEETS A0.1,1.2, 2.1,3.1A,3.1B,4.1,AND 5.1 ARE
 MISSING FROM THE PLAN SETS THAT WERE SUBMITTED. CITY
 AMENDMENTS 107.2.1
  
 2) THE PLANS ARE NOT IN THE ORDER SPECIFIED BY THE
 DRAWING INDEX ON THE COVER SHEET. CITY AMENDMENTS
 107.2.1
  
 3) SUBMIT TWO SETS OF MODEL "A" WORSE CASE ENERGY
 CALCULATIONS AND EQUIPMENT SIZING CALCULATIONS FOR THE
 MASTER PER 2010 FBC ENERGY CONSERVATION. SITE SPECIFIC
 ENERGY CALCULATIONS WILL BE REQUIRED FOR EACH PERMIT
 APPLIED FOR UNDER THE MASTER.
  
 4) SUBMIT TWO COPIES OF A GENERIC MODEL "A" SITE PLANS
 THAT INCLUDE SURFACE WATER DRAINAGE FOR THE MASTER.
 SITE SPECIFIC SITE PLANS WITH DRAINAGE SHOWN AND
 SURVEYS WILL BE REQUIRED FOR EACH PERMIT APPLIED FOR
 UNDER THE MASTER. FBC R401.3
  
 5) ON SHEET S-2 THE ALLOWABLE COMPONENT AND CLADDING
 WIND PRESSURES FOR THE WALL ZONES IN THE TABLE HAVE AN
 AREA OF 25 SQFT. THE PRESSURES SPECIFIED ON SHEET S-1
 ARE INCORRECTLY SPECIFYING THESE PRESSURES FOR OPENINGS
 THAT ARE LESS THAN 25 SQFT. FOR WORSE CASE, SPECIFY THE
 PRESSURES FOR A 10 SQFT AREA IN THE TABLE AND FOR THE
 SMALLER OPENINGS. FBC R301.2.1
  
 6) ON SHEET S-1, THERE ARE TWO SETS OF PRESSURES
 SPECIFIED FOR THE GARAGE DOOR. THIS IS ONE OPENING,
 THEREFORE, ONLY ONE SET OF PRESSURES SHOULD BE USED FOR
 IT. FBC R301.2.1
  
 7) ON SHEET S-2, UNDER CONCRETE NOTE #3, THE 1994
 EDITION OF ACI 315 IS SPECIFIED. PLEASE CHANGE TO 2008
 EDITION WHICH IS THE EDITION REFERENCED BY THE 2010
 FBCR OR JUST CURRENT EDITION. FBCR CHAPTER 43
  
 8) SUBMIT TWO SETS OF TRUSS DRAWINGS AND LAYOUTS FOR
 ASCE7-10, 170 MPH AND EXPOSURE C THAT HAVE BEEN SIGNED
 AND SEALED BY THE TRUSS ENGINEER AND REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE
 STRUCTURE. FBC R802.1.6.1 THESE ARE REQUIRED TO BE
 SUBMITTED AND REVIEWED FOR THE MASTER.
  
 9) PROVIDE STRUCTURAL DETAILS FOR THE SHED ROOFS OVER
 THE EXTERIOR DOORS ON THE LEFT AND RIGHT ELEVATIONS.
 FBC R301.1
  
 9) TWO COPIES OF PRODUCT APPROVALS ARE REQUIRED FOR
 EACH TYPE OF WINDOW AND DOOR, STRUCTURAL MULLIONS, ROOF
 COVERING, OVERHEAD GARAGE DOOR, STORM PANELS (IF IMPACT
 GLAZING IS NOT USED), BLOCK LINTELS, MANUFACTURED
 SIDING (IE HARDI-BOARD), STRUCTURAL CONNECTORS (IE
 TRUSS ANCHORS) AS REQUIRED BY DCA RULE 9N-3. NOTE:THE
 COPIED PRODUCT APPROVALS FROM MODEL B THAT WERE
 SUBMITTED ARE CURRENT & CAN BE USED IF THESE ARE THE
 PRODUCTS THAT WILL BE INSTALLED FOR THIS MODEL.
  
 10) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 SEE REVIEW COMMENTS UNDER OTHER TRADES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]