2013-01-14 12:02:23 | 1801 PALM BEACH LAKES BOULEVARD - JCP | | PERMIT #12120636 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PROVIDE A LIFE SAFETY PLAN SHOWING FIRE RATED WALLS, | | EXIT SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, | | COMMON PATH OF TRAVEL ETC. | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | NO EXIT ACCESS DOORS SHOWN IN THE "JOE FRESH" SPACE. | | | | THE SCOPE OF WORK SHOWN ON THE DEMOLITION PLAN AND THE | | OCCUPANCY PLAN SHEETS IS NOT VERY CLEAR. SHEETS APPEAR | | TO SHOWN THE INSTALLATION OF SEVERAL WALLS INDICATED AS | | D1 AND D2. NO DRAWINGS HAVE BEEN SUBMITTED INDICATING | | CHANGES TO THE LIFE SAFETY PLAN, FIRE SPRINKLER SYSTEM | | OR FIRE ALARM SYSTEM. | | | | DUE TO LACK OF PLAN INFORMATION AND SCOPE OF WORK | | CLARITY, A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE | | PERFORMED AT THIS TIME. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | |
|