Plan Review Notes For Permit 12120587 |
Permit Number |
12120587 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-12-20 12:54:28 | 1401 FORUM WAY - SUITE #600 | | PERMIT #12120587 | | MASTER #12110592 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND | | END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE | | PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE | | LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE | | THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING | | UPWARD MOVEMENT. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | |
|