Plan Review Notes For Permit 12120574 |
Permit Number |
12120574 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2013-03-07 17:48:19 | BUILDING REVIEW APPROVED WITH PROVISO: | | ***1- SOIL TEST REPORT RECOMMENDS THE FOOTINGS TO BEAR | | 1.5 FT TO 2 FT BELOW THE FINISHED GRADE (SEE SHEET 3). | | REVISE DRAWINGS AS REQUIRED. | | *** 2- REVISE ITEM #9A-2 OF THE ENERGY CALCULATIONS. | | THIS IS WOOD FRAME CONSTRUCTION NOT MASONRY. | | *** 3- REVISE PLANS TO COORDINATE WITH TRUSS PACKAGE: | | A) TRUSSES NEED BEARING AT THE ENDS TO BE 6" (SEE TRUSS | | A1 AND A2G). B) SPECIFY THE CONNECTORS FOR EXISTING | | ROOF TRUSSES TO BE RESTING ON NEW GIRDER TRUSS A2G. | | ***NOTE: IF EXISTING TRUSSES ARE CUT. PROVIDE | | ENGINEERING SHOWING HOW THE TRUSSES ARE REINFORCED TO | | PROVIDE A CONTINUOUS LOAD PATH. | | *** 4- PROVIDE PRODUCT APPROVALS FOR SIMPSON STRUCTURAL | | CONNECTOR HGT-2. NEED ONE FOR 2010 CODE NOT 2007. |
|