Plan Review Notes
Plan Review Notes For Permit 12120574
Permit Number 12120574
Review Stop B
Sequence Number 3
Notes
Date Text
2013-03-07 17:48:19BUILDING REVIEW APPROVED WITH PROVISO:
 ***1- SOIL TEST REPORT RECOMMENDS THE FOOTINGS TO BEAR
 1.5 FT TO 2 FT BELOW THE FINISHED GRADE (SEE SHEET 3).
 REVISE DRAWINGS AS REQUIRED.
 *** 2- REVISE ITEM #9A-2 OF THE ENERGY CALCULATIONS.
 THIS IS WOOD FRAME CONSTRUCTION NOT MASONRY.
 *** 3- REVISE PLANS TO COORDINATE WITH TRUSS PACKAGE:
 A) TRUSSES NEED BEARING AT THE ENDS TO BE 6" (SEE TRUSS
 A1 AND A2G). B) SPECIFY THE CONNECTORS FOR EXISTING
 ROOF TRUSSES TO BE RESTING ON NEW GIRDER TRUSS A2G.
 ***NOTE: IF EXISTING TRUSSES ARE CUT. PROVIDE
 ENGINEERING SHOWING HOW THE TRUSSES ARE REINFORCED TO
 PROVIDE A CONTINUOUS LOAD PATH.
 *** 4- PROVIDE PRODUCT APPROVALS FOR SIMPSON STRUCTURAL
 CONNECTOR HGT-2. NEED ONE FOR 2010 CODE NOT 2007.