Plan Review Notes
Plan Review Notes For Permit 12120574
Permit Number 12120574
Review Stop P
Sequence Number 1
Notes
Date Text
2013-01-02 11:02:56RESIDENTIAL (R3) ADDITION PLUMBING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE SIZE OF VENT SHOWN ON THE PLUMBING RISER
 DIAGRAM. NEED TO COMPLY WITH SEC. P3113.1 OD 2010
 FBC-RESIDENTIAL.
  
 2- ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1
 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER