Plan Review Notes For Permit 12120569 |
Permit Number |
12120569 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2012-12-21 15:19:01 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. FASTENING PROPOSED IS FOR ZONE 1 ONLY AS IT HAS A | | LIMITATION OF -60PSF. | | | | PROVIDE FASTENING FOR ZONES 2 AND 3. ENHANCED FASTENING | | TO BE IN ACCORDANCE WITH RAS117 PER GENERAL LIMITATION | | #7 OF THE NOA (LAST PAGE). REQUIRED PRESSURES FOR | | EXPOSURE, 170MPH, 15MRH ARE: ZONE 2 -63.6, ZONE 3 | | -95.7. | | | | |
|