2012-12-21 15:19:01****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FASTENING PROPOSED IS FOR ZONE 1 ONLY AS IT HAS A
 LIMITATION OF -60PSF.
  
 PROVIDE FASTENING FOR ZONES 2 AND 3. ENHANCED FASTENING
 TO BE IN ACCORDANCE WITH RAS117 PER GENERAL LIMITATION
 #7 OF THE NOA (LAST PAGE). REQUIRED PRESSURES FOR
 EXPOSURE, 170MPH, 15MRH ARE: ZONE 2 -63.6, ZONE 3
 -95.7.
  
  