2012-12-14 14:30:06629 CLEAR LAKE AVENUE
 PERMIT #12120450
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAIL: FBC SECTION 105.3.1.2: ENGINEERED FIRE ALARM
 DRAWINGS SHALL BE SIGNED AND SEALED BY A REGISTERED
 PROFESSIONAL ENGINEER (NOT AN ARCHITECT) PER FLORIDA
 STATUTE 471.
  
 PROVISO: A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION.
  
 PROVISO: FIRE ALARM CIRCUIT BREAKER TO BE MARKED IN RED
 AND IDENTIFIED AS "FIRE ALARM." PROVIDE CIRCUIT BREAKER
 LOCK FOR DEDICATED BRANCH CIRCUIT.
  