Plan Review Notes For Permit 12120418 |
Permit Number |
12120418 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-12-28 14:20:09 | *** MECHANICAL CORRECTIONS NEEDED *** | | | | 1) PLAN M-1.2 SHOWS A FAN CONTROLLER IN THE SPRINKLER | | ROOM BUT NO FAN, PLEASE CORRECT. SEE 2010 CITY OF WPB | | AMEND. 107.2.1. | | | | 2) PLAN M-1.0, M-1.1, & M 1.2 MAIN SUPPLY AIR TRUNK | | LINES AND OUTSIDE AIR DUCTS ARE NOT SIZED. SEE 2010 | | FBC/M 603.2. | | | | 3) PLAN M-1.3 AHU 1 & 2 MAIN SUPPLY AIR TRUNK LINES AND | | OUTSIDE AIR DUCTS ARE NOT SIZED. SEE 2010 FBC/M 603.2. | | | | 4) PROVIDE COOLING LOAD CALCULATIONS FOR THE THREE NEW | | A/C SYSTEMS IN THE OFFICE BUILDING. SEE 2010 FBC/ENERGY | | 503.2.1. | | | | MECHANICAL PLAN REVIEW BY: | | TOM GORDON (HY-BYRD INC.) (561) 805-6732 |
|