Plan Review Notes For Permit 12120418 |
Permit Number |
12120418 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-01-02 16:46:01 | 12120418 | | 1155 BELVEDERE ROAD | | COMMERCIAL RENOVATION | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENTS. | | | | PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE | | WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC | | ENERGY CONSERVATION CODE 505.3 | | | | PROVIDE GFCI PROTECTED RECEPTACLES WITHIN A 25 FEET | | RADIUS OF THE OUTSIDE CONDENSING UNITS. NEC 210.63 | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL | | DISCONNECTS AND FOR FLASH PROTECTION. NEC 110.22, | | 110.16 | | | | FEEDER TO PANEL ?C? APPEARS TO BE MISLABELED. | | | | NOTE: | | SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE, | | DATA AND FIRE ALARM. | | | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|