 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE
 WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC
 ENERGY CONSERVATION CODE 505.3
  
 PROVIDE GFCI PROTECTED RECEPTACLES WITHIN A 25 FEET
 RADIUS OF THE OUTSIDE CONDENSING UNITS. NEC 210.63
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 DISCONNECTS AND FOR FLASH PROTECTION. NEC 110.22,
 110.16
  
 FEEDER TO PANEL ?C? APPEARS TO BE MISLABELED.
  
 NOTE:
 SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE,
 DATA AND FIRE ALARM.
  
  