2012-12-28 16:25:27BUILDING PLAN REVIEW
 PERMIT: 12120418
 ADD:1155 BELVEDERE RD
 CONT: TBD
 TEL: (305) 710-1118
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DEC. 28/2012
 ACTION: DENIED
 1) PLEASE BREAK UP THE PROJECT INTO A PERMIT FOR EACH
 OF THE BUILDINGS WHERE WORK IS GOING TO BE PREFORMED.
 THIS PERMIT WILL BE FOR THE EXISTING BUILDING BUILT
 UNDER THE 1201 BELVEDERE ADDRESS IN 1963. PULL THE
 VALUE OUT OF THIS PERMIT AND APPLY IT APPROPRIATELY TO
 THE OTHER BUILDINGS LABELED A, B & C.
  
 2) SHEET A0.01 INDICATES A LEVEL II ALTERATION
 OCCURING, PLEASE BREAK OUT AND IDENTIFY EACH BUILDING
 BY BUILDING TYPE AND ALTERATION LEVEL FOR EACH BUILDING
 SEPERATELY. THE 1201 BELVEDERE BUILDING WILL BE
 CONSIDERED A LEVEL III ALTERATION AS WELL AS A VERTICAL
 ADDITION. PLEASE REVIEW THE REQUIREMENTS FOUND IN 2010
 EXST BLDG CODE 807.2- 807.4.1.
  
 3) 2010 FLORIDA EXIST BLDG CODE 1001.2 CREATION OR
 EXTENSION OF NONCONFORMITY. AN ADDITION SHALL NOT
 CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE ADDITION IS BEING MADE WITH
 REGARD TO ACCESSIBILITY, STRUCTURAL STRENGTH, FIRE
 SAFETY, MEANS OF EGRESS, OR THE CAPACITY OF MECHANICAL,
 PLUMBING, OR ELECTRICAL SYSTEMS.
  
 THE PROPOSED PENTHOUSE OR ARCHITECTURAL EMBELLISHMENT
 ON THE EXISTING BUILDING ADDRESSED AT 1201 BELVEDERE RD
 WAS BUILT IN 1963 UNDER THE CODE IT WAS BUILT A BLDG
 TYPE VB, THE CURRENT 2010 FBC CODE ( BLDG TYPE IIIB) IN
 1963, WHICH ALLOWED WOOD ROOF FRAMING AND SHEATHING,
 THE PROPOSED VERTICAL ADDITION IS INDICATED TO BE A
 TYPE IB SEE SHEET A0.01. UNDER THE 2010 FBC 603.1.1
 ONLY FIRE RETARDANT TREATED WOOD CAN BE USED IN THE
 ROOF SYSTEM THE PLANS INDICATE THE EXISTING ROOF
 FRAMING TO REMAIN CREATING A NONCONFORMITY.
  
 4) SHEET A1.01 INDICATES WALL SECTIONS FOUND ON SHEET
 A3.01 AND DETAILS FOUND ON A3.02 THESE PLANS DO NOT
 PROVIDE ANY MAIN WIND FORCE RESISTING SYSTEM DETAILS,
 THESE PLANS AS DRAWN ARE CONCEPTUAL, NOT PLANS THAT CAN
 BE USED FOR CONSTRUCTION DOCUMENTS,
 EXST BLDG CODE 807.2 NEW STRUCTURAL ELEMENTS.
 NEW STRUCTURAL ELEMENTS SHALL COMPLY WITH SECTION
 707.2.
  
 EXST BLDG CODE 807.3 EXISTING STRUCTURAL ELEMENTS
 CARRYING GRAVITY LOADS.
 EXISTING STRUCTURAL ELEMENTS CARRYING GRAVITY LOADS
 SHALL COMPLY WITH SECTION 707.4.
  
 5) MISSING WIND DESIGN CRITERIA:
  
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 6)
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS, DENSE GLASS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 7) SHEET A1.01 RESTROOM ENLARGED DETAIL, THE DOOR
 SWINGS IN OVER THE REQUIRED CLEAR FLOOR SPACE FOR BOTH
 THE LAV AND WATER CLOSET. 2010 ACCESSIBILITY CODE
 604.3.2 & 606.2.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO