2012-12-19 12:12:06 | *** CORRECTIONS NEEDED FOR MECHANICAL REVIEW *** | | | | 1) PROVIDE OUTDOOR AIR CALCULATIONS, SEE 2010 FBC/M | | 403.3. | | | | 2) AS SUCH A LARGE SPACE IS BEING ALTERED AND 620 CFM'S | | OF AIR IS BEING EXHAUSTED, THE ENGINEER WILL NEED TO | | STATE ON THE MECHANICAL PLAN IF AN AIR BALANCE TEST IS | | NEEDED, SEE 2010 FBC/ENERGY 503.2.9.1. | | | | MECHANICAL PLAN REVIEW BY: | | TOM GORDON (HY-BYRD INC.) (561) 805-6732 |
|