Plan Review Notes
Plan Review Notes For Permit 12120390
Permit Number 12120390
Review Stop M
Sequence Number 1
Notes
Date Text
2012-12-19 12:12:06*** CORRECTIONS NEEDED FOR MECHANICAL REVIEW ***
  
 1) PROVIDE OUTDOOR AIR CALCULATIONS, SEE 2010 FBC/M
 403.3.
  
 2) AS SUCH A LARGE SPACE IS BEING ALTERED AND 620 CFM'S
 OF AIR IS BEING EXHAUSTED, THE ENGINEER WILL NEED TO
 STATE ON THE MECHANICAL PLAN IF AN AIR BALANCE TEST IS
 NEEDED, SEE 2010 FBC/ENERGY 503.2.9.1.
  
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732