Date |
Text |
2012-12-17 10:30:13 | 1475 CENTREPARK DRIVE WEST - #135 |
| PERMIT #12120390 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING |
| SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR |
| AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL |
| HAVE "NO SMOKING" SIGNS POSTED. |
| |
| FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND |
| APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| 500 NORTH DIXIE HIGHWAY. |
| |
| EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| OCCUPANTS PERMITTED FOR EACH ROOM. |
| |
| PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| EXIT SIGNS. |
| |
| EACH FIRE RATED BARRIER SHALL BE PERMANENTLY IDENTIFIED |
| WITH SIGNS OR STENCILING READING FIRE/SMOKE |
| BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT |
| LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. |
| IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON |
| CENTER. |
| |
| WESLEY JOLIN |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| (561) 805-6730 |
| |