2012-12-27 12:08:56 | 12120348 | | 120 POTTER ROAD. | | RESIDENTIAL ADDITION | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. | | | | VERIFY THE KITCHEN RECEPTACLES SERVICING THE COUNTER | | TOPS ARE GFCI PROTECTED. NEC 210.8 | | | | INDICATE THAT ALL NEW RECEPTACLES WILL BE TAMPER | | RESISTANT. NEC 406.11 | | | | INDICATE THAT ALLL NEW GENERAL PURPOSE BRANCH CIRCUITS | | MUST BE PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. | | NEC 210.12 | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|