Plan Review Notes
Plan Review Notes For Permit 12120231
Permit Number 12120231
Review Stop M
Sequence Number 1
Notes
Date Text
2012-12-17 12:56:52*** MECHANICAL CORRECTIONS NEEDED ***
  
 1) PLAN M2 SHOWS DETAIL FOR ROOF MOUNTED CONDENSER
 UNIT. PER 2010 FBC 1509.7 MECHANICAL UNITS. ROOF
 MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS
 RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF
 SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM
 CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1509.7.
 PLEASE COMPLY WITH TABLE 1509.7.
  
 2) PLAN M1 NOTE #6 STATES CONDENSATE FROM AHU-1 TO
 DRAIN INTO MOP SINK, THIS IS PROHIBITED PER. CODE OF
 ORDINANCES CH. 90 ARTICLE III SEC 90-126. PROHIBITIONS
 AND LIMITATIONS OF DISCHARGE. (A) GENERALLY. USERS
 SHALL NOT DISCHARGE POLLUTANTS INTO THE WWF UNLESS IN
 ACCORDANCE WITH THIS ARTICLE. (B) DISCHARGE
 PROHIBITIONS. NO USER SHALL DISCHARGE INTO THE WWF ANY
 WASTE OR WASTEWATER WHICH MAY CAUSE PASS THROUGH OR
 INTERFERE WITH THE OPERATION OR PERFORMANCE OF THE WWF.
 NO USER SHALL DISCHARGE INTO THE WWF OR ANY CONNECTED
 SYSTEM ANY WASTE OR WASTEWATER CONTAINING ANY OF THE
 FOLLOWING:
 (5) STORMWATER, SURFACE WATER, GROUNDWATER, ARTESIAN
 WELL WATER, ROOF RUNOFF, SUBSURFACE DRAINAGE, SWIMMING
 POOL DISCHARGES, UNCONTAMINATED COOLING WATER,
 UNPOLLUTED INDUSTRIAL PROCESS WATERS, AIR CONDITIONING
 CONDENSATE, UNLESS SPECIFICALLY AUTHORIZED BY THE CITY
 IN WRITING.
  