2012-12-17 12:56:52 | *** MECHANICAL CORRECTIONS NEEDED *** |
| |
| 1) PLAN M2 SHOWS DETAIL FOR ROOF MOUNTED CONDENSER |
| UNIT. PER 2010 FBC 1509.7 MECHANICAL UNITS. ROOF |
| MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS |
| RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF |
| SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE |
| UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM |
| CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1509.7. |
| PLEASE COMPLY WITH TABLE 1509.7. |
| |
| 2) PLAN M1 NOTE #6 STATES CONDENSATE FROM AHU-1 TO |
| DRAIN INTO MOP SINK, THIS IS PROHIBITED PER. CODE OF |
| ORDINANCES CH. 90 ARTICLE III SEC 90-126. PROHIBITIONS |
| AND LIMITATIONS OF DISCHARGE. (A) GENERALLY. USERS |
| SHALL NOT DISCHARGE POLLUTANTS INTO THE WWF UNLESS IN |
| ACCORDANCE WITH THIS ARTICLE. (B) DISCHARGE |
| PROHIBITIONS. NO USER SHALL DISCHARGE INTO THE WWF ANY |
| WASTE OR WASTEWATER WHICH MAY CAUSE PASS THROUGH OR |
| INTERFERE WITH THE OPERATION OR PERFORMANCE OF THE WWF. |
| NO USER SHALL DISCHARGE INTO THE WWF OR ANY CONNECTED |
| SYSTEM ANY WASTE OR WASTEWATER CONTAINING ANY OF THE |
| FOLLOWING: |
| (5) STORMWATER, SURFACE WATER, GROUNDWATER, ARTESIAN |
| WELL WATER, ROOF RUNOFF, SUBSURFACE DRAINAGE, SWIMMING |
| POOL DISCHARGES, UNCONTAMINATED COOLING WATER, |
| UNPOLLUTED INDUSTRIAL PROCESS WATERS, AIR CONDITIONING |
| CONDENSATE, UNLESS SPECIFICALLY AUTHORIZED BY THE CITY |
| IN WRITING. |
| |