Plan Review Notes
Plan Review Notes For Permit 12120201
Permit Number 12120201
Review Stop B
Sequence Number 2
Notes
Date Text
2012-12-27 12:30:22****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENT FROM PREVIOUS LIST:
  
 1. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA, FBC
 1603.1.4 OR ALTERNATE METHOD FBC 2010 EXISTING BUILDING
 101.5.
  
 2ND REVIEW, PLAN NOW STATES 165MPH, EXPOSURE C.PLEASE
 EXPLAIN HOW THIS WIND SPEED HAS BEEN DETERMINED. 170MPH
 IS WORST CASE IN THE CITY OF WPB, AND THE WEBSITE
 WWW.ATCOUNCIL.ORG/WINDSPEED GIVES 169MPH AS WIND SPEED
 FOR A RISK CATEGORY II STRUCTURE.
  
 PLEASE EITHER REVISE WIND SPEED OR PROVIDE MORE
 INFORMATION AS TO HOW THE WIND SPEED OF 165MPH HAS BEEN
 DETERMINED.
  
 IN LIEU OF RESUBMITTAL, A LETTER ON THE ENGINEER'S
 LETTERHEAD CAN BE EMAILED TO ME.
  
  