Notes |
Date |
Text |
2012-12-11 06:37:21 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE FLAT | | ROOF IS FOR A CEMENTITIOUS WOOD FIBER DECK. THIS IS NOT | | THE WOOD DECK THAT IS USUALLY FOUND ON SINGLE FAMILY | | RESIDENCES. PLEASE MAKE SURE THAT THIS IS A | | CEMENTITIOUS WOOD FIBER DECK. DCA RULE 9N-3 | | | | 2) SPECIFY THE APPROVED ASSEMBLY, FASTENING OPTION AND | | MAXIMUM DESIGN PRESSURE FOR THE SYSTEM LISTED IN THE | | PRODUCT APPROVAL THAT WILL BE INSTALLED. FBC R905.9.3 | | | | 3) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 | | ENHANCED FASTENING CALCULATIONS AS REQUIRED BY | | LIMITATION NUMBER 7 ON PAGE OF THE NOA FOR THE CORNER | | AND PERIMETER ROOF AREAS. FBC R301.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|