2012-12-11 09:07:062010 FBC
  
 DENIED BY BUILDING
  
 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 DIRECT-DECK ADHERED BORAL UNDERLAYMENT SPECIFIES THE
 MAXIMUM DESIGN PRESSURE AS -45 PSF. THE PROPOSED SYSTEM
 IS A FOAM ON TILE SYSTEM WITH THE BONDED UNDERLAYMENT
 FORMING PART OF THE LOAD-PATH AND THE DESIGN UPLIFT
 PRESSURE IS TOO LOW. THIS HOUSE IS LOCATED IN EXPOSURE
 CATEGORY D WITH A WIND SPEED OF 170 MPH VULT / 132 MPH
 VASD.
  