2012-12-10 14:54:15*** PROVISO ***
  
 2010 FBC/M 306.1 ACCESS FOR MAINTENANCE AND
 REPLACEMENT.
 APPLIANCES SHALL BE ACCESSIBLE FOR INSPECTION, SERVICE,
 REPAIR AND REPLACEMENT WITHOUT DISABLING THE FUNCTION
 OF A FIRE-RESISTANCE-RATED ASSEMBLY OR REMOVING
 PERMANENT CONSTRUCTION, OTHER APPLIANCES, VENTING
 SYSTEMS OR ANY OTHER PIPING OR DUCTS NOT CONNECTED TO
 THE APPLIANCE BEING INSPECTED, SERVICED, REPAIRED OR
 REPLACED. A LEVEL WORKING SPACE AT LEAST 30 INCHES DEEP
 AND 30 INCHES WIDE (762 MM BY 762 MM) SHALL BE PROVIDED
 IN FRONT OF THE CONTROL SIDE TO SERVICE AN APPLIANCE.
  