2012-12-05 09:11:1912120101
 5900 GEORGIA AVE.
 SOLAR PV SYSTEM
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENT.
  
 PROVIDE SIGNED AND SEALED ENGINEERING FOR THE WIND LOAD
 DESIGN FOR COMPONENT AND CLADDING IN ACCORDANCE WITH
 CHAPTER 16 OF THE FLORIDA BUILDING CODE USING AN
 EFFECTIVE WIND AREA BASED ON THE DIMENSIONS OF A SINGLE
 UNIT FRAME. INDICATE THE EXPOSURE CATEGORY AND
 IMPORTANCE FACTOR FOR THE CURRENT BUILDING CODE.
 PROVIDE A FASTENING DETAIL FOR THE PANELS AND RACK
 SHOWING SIZE, TYPE AND LOCATION. 2010 FLORIDA BUILDING
 CODE SECTION 1609, ASCE 7-10
  
 VERIFY THE EXISTING ROOF SYSTEM AND STRUCTURE CAN
 SUPPORT THE SOLAR ARRAY AS PROPOSED. 2010 FBC SECTION
 1604.
  
 EACH STRUCTURE REQUIRES A SEPARATE PERMIT. ONE SET OF
 PLANS WILL BE SUFFICIENT BUT AN ADDITIONAL PERMIT
 APPLICATION WITH A SEPARATE VALUE IS NEEDED.
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  