Plan Review Notes For Permit 12120101 |
Permit Number |
12120101 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-12-05 09:11:19 | 12120101 | | 5900 GEORGIA AVE. | | SOLAR PV SYSTEM | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENT. | | | | PROVIDE SIGNED AND SEALED ENGINEERING FOR THE WIND LOAD | | DESIGN FOR COMPONENT AND CLADDING IN ACCORDANCE WITH | | CHAPTER 16 OF THE FLORIDA BUILDING CODE USING AN | | EFFECTIVE WIND AREA BASED ON THE DIMENSIONS OF A SINGLE | | UNIT FRAME. INDICATE THE EXPOSURE CATEGORY AND | | IMPORTANCE FACTOR FOR THE CURRENT BUILDING CODE. | | PROVIDE A FASTENING DETAIL FOR THE PANELS AND RACK | | SHOWING SIZE, TYPE AND LOCATION. 2010 FLORIDA BUILDING | | CODE SECTION 1609, ASCE 7-10 | | | | VERIFY THE EXISTING ROOF SYSTEM AND STRUCTURE CAN | | SUPPORT THE SOLAR ARRAY AS PROPOSED. 2010 FBC SECTION | | 1604. | | | | EACH STRUCTURE REQUIRES A SEPARATE PERMIT. ONE SET OF | | PLANS WILL BE SUFFICIENT BUT AN ADDITIONAL PERMIT | | APPLICATION WITH A SEPARATE VALUE IS NEEDED. | | | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|