Plan Review Notes For Permit 12120056 |
Permit Number |
12120056 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-02-05 11:15:18 | FBC 2010 EXISTING BUILDING CODE | | FBC 2010 ACCESSIBILITY CODE | | FBC 2010 PLUMBING REVIEW #2 | | DENIED: | | | | 403.2 SEPARATE FACILITIES. | | WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE | | FACILITIES SHALL BE PROVIDED FOR EACH SEX. | | EXCEPTIONS: | | 2. SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR FOOD | | SERVICE ESTABLISHMENTS WHICH SEAT 10 PERSONS OR LESS. | | | | IF THE RESTROOM IN THE EXISTING KITCHEN IS TO BE | | COUNTED, THE ROUTE SHALL NOT BE THROUGH THE KITCHEN, | | STORAGE, ETC. | | 403.3.1 ACCESS. | | THE ROUTE TO THE PUBLIC TOILET FACILITIES REQUIRED BY | | SECTION 403.3 SHALL NOT PASS THROUGH KITCHENS, STORAGE | | ROOMS OR CLOSETS. ACCESS TO THE REQUIRED FACILITIES | | SHALL BE FROM WITHIN THE BUILDING OR FROM THE EXTERIOR | | OF THE BUILDING. ALL ROUTES SHALL COMPLY WITH THE | | ACCESSIBILITY REQUIREMENTS OF THE FLORIDA BUILDING | | CODE, ACCESSIBILITY. THE PUBLIC SHALL HAVE ACCESS TO | | THE REQUIRED TOILET FACILITIES AT ALL TIMES THAT THE | | BUILDING IS OCCUPIED. | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|