Plan Review Notes
Plan Review Notes For Permit 12120054
Permit Number 12120054
Review Stop B
Sequence Number 1
Notes
Date Text
2012-12-11 18:35:19****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. DESIGN IS TO BE DONE IN ACCORDANCE WITH ASCE 7-10 OR
 THE AAF GUIDE PER FBC RESIDENTIAL 301. PROVIDE PLANS
 DESIGNED IN ACCORDANCE WITH ONE OF THESE METHODS. IF
 ASCE7-10 IS USED AS A DESIGN METHOD AND IS NOT PREPARED
 BY A DESIGN PROFESSIONAL, PROVIDE CALCULATIONS.
  
 2. PLAN TO INCLUDE WIND DESIGN CRITERIA FBC R 301.
  
 3. PLANS ARE TO INCLUDE THE PRINTED NAME AND SIGNATURE
 OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR THE DESIGN
 FBC 108.