Notes |
Date |
Text |
2012-12-11 18:35:19 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. DESIGN IS TO BE DONE IN ACCORDANCE WITH ASCE 7-10 OR | | THE AAF GUIDE PER FBC RESIDENTIAL 301. PROVIDE PLANS | | DESIGNED IN ACCORDANCE WITH ONE OF THESE METHODS. IF | | ASCE7-10 IS USED AS A DESIGN METHOD AND IS NOT PREPARED | | BY A DESIGN PROFESSIONAL, PROVIDE CALCULATIONS. | | | | 2. PLAN TO INCLUDE WIND DESIGN CRITERIA FBC R 301. | | | | 3. PLANS ARE TO INCLUDE THE PRINTED NAME AND SIGNATURE | | OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR THE DESIGN | | FBC 108. |
|