Plan Review Notes For Permit 12110743 |
Permit Number |
12110743 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-12-04 10:25:42 | 2475 MERCER AVENUE - #201 | | PERMIT #12110743 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | EACH FIRE-RATED BARRIER SHALL BE PERMANENTLY IDENTIFIED | | WITH SIGNS OR STENCILING READING FIRE/SMOKE | | BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT | | LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. | | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON | | CENTER. | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE | | ALARM SYSTEM. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 |
|