2013-02-13 12:49:41 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2010 |
| FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| |
| FROM PREVIOUS LIST: |
| |
| 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, |
| SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING |
| CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR |
| BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING |
| CANNOT BE REDUCED BY MORE THAN 5%. |
| |
| 2ND REVIEW, CODE COMPLIANCE FOR EMERGENCY MEANS OF |
| ESCAPE AND RESCUE HAS NOT BEEN SHOWN FOR THE FOLLOWING |
| ROOMS: |
| |
| BEDROOM, FIRST FLOOR, OPENINGS M, N, O ARE ALL FIXED |
| WINDOWS. PLEASE SHOW EMERGENCY MEANS OF ESCAPE AND |
| RESCUE FOR THIS ROOM, AS WELL AS CLEAR OPENING |
| DIMENSIONS. REVISE WINDOW SCHEDULE AS NECESSARY. |
| |
| BEDROOM 2ND FLOOR, WINDOWS P AND Q CASEMENT, SIZE AND |
| CLEAR OPENING NOT CLEAR. THE DIMENSIONS, 22X46, DO NOT |
| CORRELATE WITH THE PHOTOGRAPHS PROVIDED AND THE |
| DIMENSIONS PROVIDED BY PREVIOUS CONTRACTOR. 22" DOES |
| NOT MEET THE MINIMUM WIDTH FOR EMERGENCY ESCAPE AND |
| RESCUE, BUT THE PHOTOGRAPH FOR EAST ELEVATION SHOWS A |
| WIDER WINDOW. PLEASE SHOW COMPLIANCE FOR FBC R 310. |
| |
| BEDROOMS ON 2ND FLOOR WITH WINDOWS R THROUGH U, WINDOW |
| HEIGHTS DO NOT MEET REQUIREMENT FOR EMERGENCY ESCAPE |
| AND RESCUE. PROVIDE INFORMATION REQUESTED - EXISTING |
| WINDOW TYPE, CLEAR OPENING. |
| |
| PLEASE NOTE THAT ONLY ONE EMERGENCY ESCAPE AND RESCUE |
| OPENING IS REQUIRED FOR EACH BEDROOM. |
| |
| 2. OK |
| |
| 3. OK |
| |
| NEW COMMENT: |
| |
| 4. THE INSPECTION LETTER FROM THE ENGINEER IS CONFUSING |
| AS IT IS FOR STRUCTURAL STEEL CONNECTIONS. NO |
| STRUCTURAL STEEL SHOWN ON THE PLAN. |
| |
| ALSO, PHOTOGRAPHS SHOW THAT ONE WINDOW WILL BE |
| ELIMINATED. PROVIDE A STRUCTURAL DETAIL FOR CLOSING THE |
| OPENING. |
| |
| |
| |