2012-12-27 11:18:55 | *** PROVISO *** |
| 1) SUBMIT AN UP TO DATE PRODUCT APPROVAL FOR THE NEW |
| A/C CONDENSER STAND, FOR REVIEW BEFORE FINAL MECHANICAL |
| INSPECTION. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS |
| RULE 9N-3 NOV. 1, 2010, (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: (G) EXTERIOR COOLER, FREEZERS & |
| "PER-ENGINEERED A/C STANDS". ALSO SEE 2010 FBC |
| 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| 2) CONDENSATE WATER FROM AHU-1 CAN NOT DISCHARGE INTO |
| THE CITY WASTEWATER, PER CITY OF ORDINANCES CITY OF WPB |
| CH.90 ARTICLE III SEC. 90-126. PROHIBITIONS AND |
| LIMITATIONS OF DISCHARGE. (A) GENERALLY. USERS SHALL |
| NOT DISCHARGE POLLUTANTS INTO THE WWF UNLESS IN |
| ACCORDANCE WITH THIS ARTICLE. (B) DISCHARGE |
| PROHIBITIONS. NO USER SHALL DISCHARGE INTO THE WWF ANY |
| WASTE OR WASTEWATER WHICH MAY CAUSE PASS THROUGH OR |
| INTERFERE WITH THE OPERATION OR PERFORMANCE OF THE WWF. |
| NO USER SHALL DISCHARGE INTO THE WWF OR ANY CONNECTED |
| SYSTEM ANY WASTE OR WASTEWATER CONTAINING ANY OF THE |
| FOLLOWING: (5) STORM-WATER, SURFACE WATER, GROUNDWATER, |
| ARTESIAN WELL WATER, ROOF RUNOFF, SUBSURFACE DRAINAGE, |
| SWIMMING POOL DISCHARGES, UNCONTAMINATED COOLING WATER, |
| UNPOLLUTED INDUSTRIAL PROCESS WATERS, AIR CONDITIONING |
| CONDENSATE, UNLESS SPECIFICALLY AUTHORIZED BY THE CITY |
| IN WRITING. SEE 2010 FBC/M 307.2.1. |
| 3) OFFICE 12 MAY NEED A R/A Z-BOOT, SEE 2010 FBC/M |
| 601.4. |