Plan Review Notes
Plan Review Notes For Permit 12110638
Permit Number 12110638
Review Stop M
Sequence Number 2
Notes
Date Text
2012-12-27 11:18:55*** PROVISO ***
 1) SUBMIT AN UP TO DATE PRODUCT APPROVAL FOR THE NEW
 A/C CONDENSER STAND, FOR REVIEW BEFORE FINAL MECHANICAL
 INSPECTION. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS
 RULE 9N-3 NOV. 1, 2010, (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (G) EXTERIOR COOLER, FREEZERS &
 "PER-ENGINEERED A/C STANDS". ALSO SEE 2010 FBC
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 2) CONDENSATE WATER FROM AHU-1 CAN NOT DISCHARGE INTO
 THE CITY WASTEWATER, PER CITY OF ORDINANCES CITY OF WPB
 CH.90 ARTICLE III SEC. 90-126. PROHIBITIONS AND
 LIMITATIONS OF DISCHARGE. (A) GENERALLY. USERS SHALL
 NOT DISCHARGE POLLUTANTS INTO THE WWF UNLESS IN
 ACCORDANCE WITH THIS ARTICLE. (B) DISCHARGE
 PROHIBITIONS. NO USER SHALL DISCHARGE INTO THE WWF ANY
 WASTE OR WASTEWATER WHICH MAY CAUSE PASS THROUGH OR
 INTERFERE WITH THE OPERATION OR PERFORMANCE OF THE WWF.
 NO USER SHALL DISCHARGE INTO THE WWF OR ANY CONNECTED
 SYSTEM ANY WASTE OR WASTEWATER CONTAINING ANY OF THE
 FOLLOWING: (5) STORM-WATER, SURFACE WATER, GROUNDWATER,
 ARTESIAN WELL WATER, ROOF RUNOFF, SUBSURFACE DRAINAGE,
 SWIMMING POOL DISCHARGES, UNCONTAMINATED COOLING WATER,
 UNPOLLUTED INDUSTRIAL PROCESS WATERS, AIR CONDITIONING
 CONDENSATE, UNLESS SPECIFICALLY AUTHORIZED BY THE CITY
 IN WRITING. SEE 2010 FBC/M 307.2.1.
 3) OFFICE 12 MAY NEED A R/A Z-BOOT, SEE 2010 FBC/M
 601.4.
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732