2012-12-04 16:04:01 | MECHANICAL PLAN REVIEW | | PERMIT: 12110638 | | ADD: 319 CLEMATIS ST # 502 | | CONT: CLAY KOHLMEYER | | TEL: (561)694-1214 | | | | 2010 FLORIDA BUILDING CODE W | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DEC. 04/2012 | | ACTION: DENIED | | | | 1) CONFERENCE ROOM # 02 THE TENANT SEPERATION WALL IS | | MISSING A FIRE DAMPER IN ACCORDANCE WITH FBC-B 716.5.4. | | IT ALSO APPEARS THAT THE RESTROOM AND BREAKROOM EXHAUST | | AT THE TENANT SEPERATION WALL IS MISSING A FIRE DAMPER. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | CONSTRUCTION SERVICES HOME PAGE | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | |
|