Plan Review Notes For Permit 12110638 |
Permit Number |
12110638 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-12-04 10:56:51 | 319 CLEMATIS STREET - SUITE #502 | | PERMIT #12110638 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | SHEET M2: NO EXISTING FIRE DAMPER SHOWN IN DUCTWORK | | PENETRATING CONFERENCE ROOM #2. | | | | ELECTRICAL: NO ENGINEERED FIRE ALARM DRAWINGS | | SUBMITTED. | | | | FIRE SPRINKLERS: FOR SYSTEM PRESSURES EXCEEDING 100 | | PSI, ARMOVERS AND END OF BRANCH LINE PENDENT SPRINKLERS | | SHALL BE PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL | | BE LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE | | THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING | | UPWARD MOVEMENT. | | | | SHEET FS2: PLAN INDICATES THIS IS FOR THE 7TH FLOOR | | (SHOULD BE 5TH FLOOR). | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | |
|