 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET M2: NO EXISTING FIRE DAMPER SHOWN IN DUCTWORK
 PENETRATING CONFERENCE ROOM #2.
  
 ELECTRICAL: NO ENGINEERED FIRE ALARM DRAWINGS
 SUBMITTED.
  
 FIRE SPRINKLERS: FOR SYSTEM PRESSURES EXCEEDING 100
 PSI, ARMOVERS AND END OF BRANCH LINE PENDENT SPRINKLERS
 SHALL BE PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL
 BE LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE
 THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING
 UPWARD MOVEMENT.
  
 SHEET FS2: PLAN INDICATES THIS IS FOR THE 7TH FLOOR
 (SHOULD BE 5TH FLOOR).
  