2012-12-04 16:02:26 | BUILDING PLAN REVIEW |
| PERMIT: 12110638 |
| ADD: 319 CLEMATIS ST # 502 |
| CONT: CLAY KOHLMEYER |
| TEL: (561)694-1214 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DEC. 04/2012 |
| ACTION: DENIED |
| |
| 1) PLEASE REVIEW SHEET A-1.0 THE NEW EXECUTIVE BATHROOM |
| DOOR AND ENTRY DOOR THERE IS LESS THAN 4'-0" BETWEEN |
| DOORS, PLEASE SEE 2010 FBC ACCESSIBLITY CODE |
| 404.2.6 DOORS IN SERIES. |
| |
| 2) CONFERENCE ROOM # 02 THE TENANT SEPERATION WALL IS |
| MISSING A FIRE DAMPER IN ACCORDANCE WITH FBC-B 716.5.4. |
| IT ALSO APPEARS THAT THE RESTROOM AND BREAKROOM EXHAUST |
| AT THE TENANT SEPERATION WALL IS MISSING A FIRE DAMPER. |
| |
| JAMES A. WITMER CBO |