Plan Review Notes
Plan Review Notes For Permit 12110631
Permit Number 12110631
Review Stop E
Sequence Number 1
Notes
Date Text
2012-12-05 13:26:4212110631
 3110 45TH STREET
 SOLAR PV SYSTEM
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENT.
  
 INDICATE ON PLANS THE TYPE, LOCATION AND MATERIAL OF
 ALL REQUIRED ELECTRICAL SAFETY SIGNS/PLAQUES WITH
 SPECIFIC WORDING FOR EACH REQUIRED LOCATION. SIGN MUST
 BE LEGIBLE, INDELIBLE, PERMANENT AND SUITABLE FOR THE
 LOCATION AND ENVIRONMENT. NEC 690.5 (C), 690.35(F),
 690.70, 690.53, 690.56, 705 10, 705.12(D)(7)
  
 INDICATE THE WIRING METHOD PROPOSED ( IE. METAL ,
 CONDUIT, CABLE ETC). NEC 690.31(E)
  
 PROVIDE SPECIFICATIONS ON THE INVERTER AND PANELS. NEC
 110.3
  
  