| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| RECEPTION AREA - GROUND FLOOR: BOTH THE FBC AND NFPA |
| 101 REQUIRE THE FLOOR-TO-FLOOR "CONVENIENCE OPENING" TO |
| BE SEPARATED FROM THE CORRIDORS. THE CURRENT DESIGN |
| CREATES A FLOOR/CEILING OPENING FROM THE GROUND FLOOR |
| TO THE FIRST FLOOR THAT IS COMPLETELY OPEN |
| (NON-SEPARATED) FROM THE CORRIDORS. |
| |
| FBC |
| 708.2 SHAFT ENCLOSURE REQUIRED. |
| OPENINGS THROUGH A FLOOR/CEILING ASSEMBLY SHALL BE |
| PROTECTED BY A SHAFT ENCLOSURE COMPLYING WITH THIS |
| SECTION. |
| 7.0 IN OTHER THAN GROUPS I-2 AND I-3, A SHAFT ENCLOSURE |
| IS NOT REQUIRED FOR A FLOOR OPENING OR AN AIR TRANSFER |
| OPENING THAT COMPLIES WITH THE FOLLOWING: |
| 7.1. DOES NOT CONNECT MORE THAN TWO STORIES. |
| 7.2. IS NOT PART OF THE REQUIRED MEANS OF EGRESS |
| SYSTEM. |
| 7.3. IS NOT CONCEALED WITHIN THE CONSTRUCTION OF A WALL |
| OR A FLOOR/CEILING ASSEMBLY. |
| 7.4 IS NOT OPEN TO A CORRIDOR IN GROUP I AND R |
| OCCUPANCIES. |
| 7.5. IS NOT OPEN TO A CORRIDOR ON NONSPRINKLERED FLOORS |
| IN ANY OCCUPANCY. |
| 7.6 IS SEPARATED FROM FLOOR OPENINGS AND AIR TRANSFER |
| OPENINGS SERVING OTHER FLOORS BY CONSTRUCTION |
| CONFORMING TO REQUIRED SHAFT ENCLOSURES. |
| 7.7. IS LIMITED TO THE SAME SMOKE COMPARTMENT. |
| |
| LIFE SAFETY CODE |
| 8.6.8 CONVENIENCE OPENINGS. |
| 8.6.8.1 A VERTICAL OPENING SERVING AS OTHER THAN AN |
| EXIT ENCLOSURE, CONNECTING ONLY TWO ADJACENT STORIES |
| AND PIERCING ONLY ONE FLOOR, SHALL BE PERMITTED TO BE |
| OPEN TO ONE OF THE TWO STORIES. |
| 8.6.8.2 WHERE PERMITTED BY CHAPTERS 11 THROUGH 43, |
| UNENCLOSED VERTICAL OPENINGS NOT CONCEALED WITHIN THE |
| BUILDING CONSTRUCTION SHALL BE PERMITTED AS FOLLOWS: |
| (1) SUCH OPENINGS SHALL CONNECT NOT MORE THAN TWO |
| ADJACENT STORIES (ONE FLOOR PIERCED ONLY). |
| (2) SUCH OPENINGS SHALL BE SEPARATED FROM UNPROTECTED |
| VERTICAL OPENINGS SERVING OTHER FLOORS BY A BARRIER |
| COMPLYING WITH 8.6.5. |
| (3) SUCH OPENINGS SHALL BE SEPARATED FROM CORRIDORS. |
| (4) IN NEW CONSTRUCTION, THE CONVENIENCE OPENING SHALL |
| BE SEPARATED FROM THE CORRIDOR REFERENCED IN 8.6.8.2(3) |
| BY A SMOKE PARTITION, UNLESS CHAPTERS 11 THROUGH 43 |
| REQUIRE THE CORRIDOR TO HAVE A FIRE RESISTANCE RATING. |
| (5) SUCH OPENINGS SHALL NOT SERVE AS A REQUIRED MEANS |
| OF EGRESS. |
| |