Plan Review Notes For Permit 12110598 |
Permit Number |
12110598 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-11-27 15:27:17 | 12110598 | | 726 NEW YORK ST. | | RESIDENTIAL REMODEL | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. | | | | PROVIDE A REVISED ELECTRIC SERVICE RISER PLAN WITH | | PANELS, MAIN BREAKERS, MAIN DISCONNECTS, WIRE SIZES, | | GROUNDING ETC. SHOW LOCATION OF ALL PANEL BOARDS. NEC | | 215.15 | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | SERVICE GROUND. NEC 250.94 | | | | A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE | | BACK ENTRANCE AREA. NEC 210.52 | | (E) | | | | THE NEW BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH | | CIRCUIT. NEC 210.11 (C) (3) | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|