 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE A REVISED ELECTRIC SERVICE RISER PLAN WITH
 PANELS, MAIN BREAKERS, MAIN DISCONNECTS, WIRE SIZES,
 GROUNDING ETC. SHOW LOCATION OF ALL PANEL BOARDS. NEC
 215.15
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE
 BACK ENTRANCE AREA. NEC 210.52
 (E)
  
 THE NEW BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  