2012-12-05 09:47:20BUILDING PLAN REVIEW
 PERMIT: 12110585
 ADD: 5200 EAST AVE - TEMP KITCHEN, STORAGE & DINING
 AREA.
 CONT: KENNEDY CONSTRUCTION
 TEL: (561)434-1300
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DEC. 05/ 2012
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION AND ARCHITECTURAL PLANS
 INDICATE THE USE OF MANUFACTURED BUILDINGS BEING USED
 AS A TEMPORARY KITCHEN, STORAGE ROOMS, RESTROOMS &
 DINING AREA. THE STATE APPROVED MODULAR BUILDING PLANS
 DESIGN CRITERIA INDICATE THIS STRUCTURE WAS DESIGNED TO
 A BUSINESS OCCUPANCY, PLEASE REVIEW FLORIDA STATUTES IN
 REGARDS TO MANUFACTURED BUILDINGS AND REQUIRED
 RECERTIFICATION OF MANUFACTURED BUILDINGS.
  
 553.375.RECERTIFICATION OF MANUFACTURED BUILDINGS.PRIOR
 TO THE RELOCATION TO A SITE THAT HAS A HIGHER DESIGN
 WIND SPEED, MODIFICATION, OR CHANGE OF OCCUPANCY OF A
 MANUFACTURED BUILDING WITHIN THE STATE, THE
 MANUFACTURER, DEALER, OR OWNER THEREOF MAY APPLY TO THE
 DEPARTMENT FOR RECERTIFICATION OF THAT MANUFACTURED
 BUILDING. THE DEPARTMENT SHALL, BY RULE, PROVIDE WHAT
 INFORMATION THE APPLICANT MUST SUBMIT FOR
 RECERTIFICATION AND FOR PLAN REVIEW AND INSPECTION OF
 SUCH MANUFACTURED BUILDINGS AND SHALL ESTABLISH FEES
 FOR RECERTIFICATION. UPON A DETERMINATION BY THE
 DEPARTMENT THAT THE MANUFACTURED BUILDING COMPLIES WITH
 THE APPLICABLE BUILDING CODES, THE DEPARTMENT SHALL
 ISSUE A RECERTIFICATION INSIGNIA. A MANUFACTURED
 BUILDING THAT BEARS RECERTIFICATION INSIGNIA DOES NOT
 REQUIRE ANY ADDITIONAL APPROVAL BY AN ENFORCEMENT
 JURISDICTION IN WHICH THE BUILDING IS SOLD OR
 INSTALLED, AND IS CONSIDERED TO COMPLY WITH ALL
 APPLICABLE CODES. AS AN ALTERNATIVE TO RECERTIFICATION
 BY THE DEPARTMENT, THE MANUFACTURER, DEALER, OR OWNER
 OF A MANUFACTURED BUILDING MAY SEEK APPROPRIATE
 PERMITTING AND A CERTIFICATE OF OCCUPANCY FROM THE
 LOCAL JURISDICTION IN ACCORDANCE WITH PROCEDURES
 GENERALLY APPLICABLE UNDER THE FLORIDA BUILDING CODE.
  
 1A) IT WOULD APPEAR THAT THE HANLEY CENTER WILL NEED TO
 DECIDE IF THEY ARE GOING TO THE STATE TO GET THIS
 MANUFACTURERED BUILDING RECERTIFIED FOR THE CHANGE OF
 OCCUPANCY OR IF THEY ARE GOING TO HAVE THE BUILDING
 DEPARTMENT DO A COMPLETE REVIEW UNDER THE CURRENT 2010
 FLORIDA BUILDING CODE.
  
 1B) THE STATE APPROVED PLAN WIND DESIGN CRITERIA WAS
 FOR A WIND EXPOSURE CATEGORY "B", THE NEW SITE LOCATION
 IS CONSIDERED A CATEGORY "C".WIND EXPOSURE,
 1609.4.1 WIND DIRECTIONS AND SECTORS.
 1609.4.2 SURFACE ROUGHNESS CATEGORIES.
 SURFACE ROUGHNESS C. OPEN TERRAIN WITH SCATTERED
 OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS THAN 30 FEET
 (9144 MM). THIS CATEGORY INCLUDES FLAT OPEN COUNTRY AND
 GRASSLANDS.THIS SURFACE ROUGHNESS SHALL ALSO APPLY TO
 ANY BUILDING LOCATED WITHIN SURFACE ROUGHNESS B-TYPE
 TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF SURFACE
 ROUGHNESS C OR D-TYPE TERRAIN THAT EXTENDS MORE THAN
 600 FEET (182.9 M) AND WIDTH GREATER THAN 150 FEET IN
 THE UPWIND DIRECTION.
  
 1C) (1)THE STATE APPROVED PLANS ALSO INDICATE UNDERTHE
 HEADING STRUCTURAL LOAD LIMITATIONS (8) THIS BUILDING
 IS NOT DESIGNED TO BE SUBMERGED IF LOCATED IN A FLOOD
 HAZARD AREA. THIS PROPOSED MANUFACTURED BUILDING WILL
 AS ILLUSTRATED, BE LOCATED IN A "AH" FLOODZONE THE BASE
 FLOOD ELEVATION OF 17'-0" NGVD PLUS AN ADDITIONAL 6
 INCHES OF HEIGHT CITY REQUIREMENT SEE CITY MUIN CODE
 SECTION 94-546. FOR MANUFACTURED BUILDINGS AS WELL AS
 MOBILE HOMES, THIS ELEVATION IS TO THE UNDERSIDE OF THE
 CARRIAGE, NOT FINISH FLOOR. THE STATE APPROVED PLANS
 FOR THE FOUNDATION PAGE DOES NOT INCLUDE THE PRESSURES
 DUE TO MOVING WATER, A ENGINEERED FOUNDATION PLAN WILL
 BE REQUIRED.
  
 1C)(2) ANY ATTENDANT UTILITES, ELECTRIC & MECHANICAL
 EQUIPMENT WILL NEED TO BE LOCATED ABOVE THE 17'-6" NGVD
 ELEVATION. CITY MUNI CODE 94-546 .
  
 1C)(3) FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN
 "A" FLOOD ZONE. A (3) FLOOD ELEVATION CERTIFICATE WILL
 BE REQUIRED:
 1) TO BE SUBMITTED FOR PERMIT REVIEW FOR THE PROPOSED
 ELEVATION, WITH NOTES!!!!
 2) ONCE THE MANUFACTURED BUILDING IS ISNSTALLED
 3) BEFORE THE ISSUANCE OF C.O. WITH ALL ASSOCIATED
 ELEVATIONS OF ANY ELECTRICAL OR MECHANICAL EQUIPMENT,
 WITH NOTES!!!
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES: JULY 31,2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2012, THROUGH JULY 31/ 2015.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 SEPTEMBER 30/ 2013. ALTHOUGH THE OLD VERSION OF THE
 FORM IS NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING
 COPIES MAY BE USED UNTIL SEPTEMBER 30/2013. ELEVATIONS
 CERTIFIED ON OR AFTER OCTOBER 1/2013, MUST BE SUBMITTED
 ON THE NEW FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 1D) PLEASE PROVIDE STORM SHUTTER PRODUCT APPROVALS (2)
 COPIES AND PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT
 GLAZING. FBC 1609.1.4.
  
 FL BLD CODE 2004 SECTION 106.3.3, 1609.1.4, 1714.5.1 &
 EXIST BUILD CODE 507.3. PROCEDURES: 1(B) A COMPLETE
 INSTALLATION SCHEDULE SUMMARIZING & IDENTIFYING OPENING
 SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT
 SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS,
 WALL PRESSURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION TO FACILITATE
 PLAN REVIEW AND PERMIT ISSUANCE.
  
 1E) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 1F) THE STATE APPROVED PLANS ARE FOR (3) 11'-8" WIDE
 MODULES WHEREAS THE THE FLOOR PLAN INDICATES AN
 ADDITIONAL RESTROOM AND CONNECTED HALLWAY AS WELL AS
 TWO
 STORAGE UNITS, WHAT WILL THESE ADDITIONAL UNITS BE
 COVERED UNDER, MODULAR BUILDINGS OR SITE BUILT
 CONSTRUCTION? ADDITIONAL INFOMATION IS REQUIRED.
 107.2.1.
  
 2) SHEET A-1:
  
 2A) THE DECK AND STAIR GAURDRAILS ARE DESIGNED AS FOR A
 FACTORY OCCUPANCY, NOT A ASSEMBLY OCCUPANCY, PLEASE
 REVIEW 2010 FBC-B 1013.2 FOR REQUIRED HEIGTH OF 42
 INCHES AND 1013.3 OPENING LIMITATIONS.
  
 2B) THE PLANS DO NOT INDICATE THE SLOPE OF THE DECK
 1010.2 SLOPE NOR IF THERE IS A BOTTOM OR TOP LANDING
 AREAS INDICATED ON THE PLANS. THE TOP AND BOTTOM
 LANDINGS ARE TO BE 60 INCHES MINIMUM IN THE DIRECTION
 OF TRAVEL. 1010.6.4 CHANGE OF DIRECTION THE LANDING
 REQUIRES A LANDING SIZE OF 60X60 INCHES SEE 1010.6.4.
  
 3) THE PLANS DO NOT PROVIDE AS TO THE WIND DESIGN
 CRITERIA PER 1609.1.1.
  
 4) THE DESIGN OF THE STAIRS, RAMP NOR RAISED PLATFORM
 IS NOT PROVIDED IN REGARDS TO LIVE LOADS PER 2010 FBC-B
 TABLE 1607.1.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  