2012-11-20 15:57:42PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
 VERIFY THE REQUIRED WORKING CLEARANCES AND DEDICATED
 WORKING SPACE HAS BEEN PROVIDED AT THE ELECTRICAL
 SERVICE. NEC 110.26, 240.24
 PROVIDE A LOAD CALCULATION FOR THE MAIN SERVICE FEED.
 NEC 220.40
  