2012-12-20 15:28:45 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2010 |
| FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| |
| COMMENTS FROM PREVIOUS LIST: |
| |
| 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| |
| 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. |
| |
| 3. IF THE PROPOSED PRODUCT DOES NOT MEET THE MINIMUM |
| STC AND IIC RATINGS AND AN UNDERLAYMENT IS PROPOSED, |
| PROVIDE SPEC SHEETS. UNDERLAYMENT IS REQUIRED TO COMPLY |
| WITH FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| 2ND REVIEW - PROVIDE A COPY OF TEST DATA FOR STC, IIC, |
| AND FLAME SPREAD. THE "MEGASHEET" SUBMITTED DOES NOT |
| STATE HOW THE DATA WAS OBTAINED. IT IS ALSO NOT CLEAR |
| WHETHER THE "MEGASHEET" IS FOR THE ATTACHED CORK OR IF |
| AN ADDITIONAL UNDERLAYMENT IS PROPOSED. |
| |
| |
| |