Plan Review Notes For Permit 12110516 |
Permit Number |
12110516 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-11-21 09:37:51 | BUILDING PLAN REVIEW | | PERMIT: 12110516 | | ADD: 300 53RD ST | | CONT: STORM ROOFING | | TEL: (561)687-0268 | | | | 2010 FLORIDA BUILDING CODE W | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1) THE SUBMITTED RAS 117 CALCUALTION IS FOR USE WITH | | NOA 10-0125.05 GAF RUBEROID MODIFIED BITUMEN ROOF | | SYSTEM OVER STEEL DECK,WHERE AS THE NOA SUBMIITED | | 12-0619.10 IS A TAMKO MODIFIED BITUMEN ROOF SYSTEM OVER | | STEEL DECK SYSTEM, DISCREPANCIES, I SPOKE WITH THE | | CONTRRACTOR, HE WILL RESUBMIT NEW RAS 117 CALCULATIONS | | FOR THE TAMKO MODIFIED BITUMEN PRODUCT. |
|