Plan Review Notes For Permit 12110424 |
Permit Number |
12110424 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-11-19 12:53:53 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. RAS 117 CALCULATIONS DO NOT APPEAR CORRECT. | | | | SEE PERIMETER ZONE SPACING REQUIREMENT, RATHER THAN 7" | | ZONE 2 SPACING SHOULD BE 6" MINIMUM FOR 3 FIELD ROWS. | | IT APPEARS THAT ENGINEER MAY HAVE USED ROW SPACING OF | | 6.4" FOR FOUR ROWS RATHER THAN 8" FOR THREE FIELD ROWS. | | | | CORNER ZONE APPEARS TO HAVE SAME ERROR; IT APPEARS THAT | | 5.33 MAY HAVE BEEN USED FOR ROW SPACING DIMENSION BUT | | THIS IS THE SPACING FOR FIVE FIELD ROWS (SIX TOTAL), | | SHOULD USE 6.4" FOR FOUR FIELD ROWS. | | | | CHECK = 36" BASE SHEET, - 4" LAP = 32" | | 32" / 4 ROWS TOTAL = 8" (ONE LAP ROW, THREE FIELD ROWS) | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU FEEL THAT I AM IN | | ERROR OR IF YOU NEED ANY FURTHER ASSISTANCE. | | | | | | | | |
|