Plan Review Notes
Plan Review Notes For Permit 12110424
Permit Number 12110424
Review Stop B
Sequence Number 1
Notes
Date Text
2012-11-19 12:53:53****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. RAS 117 CALCULATIONS DO NOT APPEAR CORRECT.
  
 SEE PERIMETER ZONE SPACING REQUIREMENT, RATHER THAN 7"
 ZONE 2 SPACING SHOULD BE 6" MINIMUM FOR 3 FIELD ROWS.
 IT APPEARS THAT ENGINEER MAY HAVE USED ROW SPACING OF
 6.4" FOR FOUR ROWS RATHER THAN 8" FOR THREE FIELD ROWS.
  
 CORNER ZONE APPEARS TO HAVE SAME ERROR; IT APPEARS THAT
 5.33 MAY HAVE BEEN USED FOR ROW SPACING DIMENSION BUT
 THIS IS THE SPACING FOR FIVE FIELD ROWS (SIX TOTAL),
 SHOULD USE 6.4" FOR FOUR FIELD ROWS.
  
 CHECK = 36" BASE SHEET, - 4" LAP = 32"
 32" / 4 ROWS TOTAL = 8" (ONE LAP ROW, THREE FIELD ROWS)
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU FEEL THAT I AM IN
 ERROR OR IF YOU NEED ANY FURTHER ASSISTANCE.
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved