Plan Review Notes
Plan Review Notes For Permit 12110363
Permit Number 12110363
Review Stop P
Sequence Number 1
Notes
Date Text
2012-12-05 13:01:38FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
  
 PLUMBING DRAWINGS ARE OK *NOTE THAT THE LAVATORY ON THE
 FLAT DRAWING IS LISTED AS P-2 WHICH THE FIXTURE
 SCHEDULE LISTS AS A URINAL.
  
 SHEET EGA-1 THE RESTROOM IS SHOWN AS 6'-10". TO MEET
 THE REQUIREMENTS OF ACCESSIBILITY 604.3.2, ( 60"
 UNOBSTRUCTED CLEAR SPACE) THE INSIDE MINIMUM WOULD BE
 7'-1".
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR