2012-11-19 13:26:123401 PARKER AVENUE - MAIN ENTRY GUARD BUILDING
 PERMIT #12110363
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A NAME, ADDRESS OR LETTER ON THE BUILDING SO
 THE LOCATION CAN BE IDENTIFIED BY EMERGENCY RESPONDERS.
 NUMBERS/LETTERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT
 WITH 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY.
  
 STRUCTURES WITH LIGHT FRAME ROOF TRUSS CONSTRUCTION
 SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO THE
 BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE LETTER R.
  