2012-11-20 13:09:33FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
  
 1. TWO SINKS AND THE WASHING MACHINE THAT ARE SHOWN ON
 THE PLANS ARE NOT SHOWN ON THE ISOMETRIC DRAWINGS.
  
 2. IF THE OCCUPANCY LOAD IS OVER 15, A HI/LO DRINKING
 FOUNTAIN WILL BE REQUIRED.
 FBC PLUMBING 2010 403.1 (E & F)
 FBC 2010 ACCESSIBILITY 211.2
  
 3. FRONT CLEARANCE FOR THE WATER CLOSET IS REQUIRED TO
 BE 56" FROM THE REAR WALL.
 FBC 2010 ACCESSIBILITY 604.3.1
  
 4. THE SHOWER DOES NOT MEET THE REQUIREMENTS OF:
 FBC 2010 ACCESSIBILITY 608.2.1
  
  