2012-11-20 13:09:33 | FBC 2010 ACCESSIBILITY CODE | | FBC 2010 PLUMBING REVIEW #1 | | DENIED: | | | | | | 1. TWO SINKS AND THE WASHING MACHINE THAT ARE SHOWN ON | | THE PLANS ARE NOT SHOWN ON THE ISOMETRIC DRAWINGS. | | | | 2. IF THE OCCUPANCY LOAD IS OVER 15, A HI/LO DRINKING | | FOUNTAIN WILL BE REQUIRED. | | FBC PLUMBING 2010 403.1 (E & F) | | FBC 2010 ACCESSIBILITY 211.2 | | | | 3. FRONT CLEARANCE FOR THE WATER CLOSET IS REQUIRED TO | | BE 56" FROM THE REAR WALL. | | FBC 2010 ACCESSIBILITY 604.3.1 | | | | 4. THE SHOWER DOES NOT MEET THE REQUIREMENTS OF: | | FBC 2010 ACCESSIBILITY 608.2.1 | | | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|