2012-11-30 10:07:39 | 250 SOUTH AUSTRALIAN AVENUE - SUITE #200 |
| PERMIT #12110332 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| LIFE SAFETY PLAN: NO EXIT SIGNAGE PROVIDED ON PLANS. |
| |
| SHEET A1-0: THE ADJACENT TENANT SPACE APPEARS TO ONLY |
| HAVE ACCESS TO ONE EXIT (EAST STAIR). |
| |
| SHEET A1-0: SEVERAL EXIT ACCESS DOORS ARE EQUIPPED WITH |
| KEYPADS THAT WILL PROHIBIT OCCUPANTS FROM FREE ACCESS |
| TO A SECONDARY EXIT (WEST STAIR). DOORS REQUIRE FREE |
| EGRESS OR MUST COMPLY WITH THE FOLLOWING: |
| |
| SECTION 7.2.1.6.2 OF NFPA 101 FLORIDA EDITION 2009 |
| ALLOWS ACCESS CONTROLLED EGRESS DOORS PROVIDED THAT ALL |
| SEVEN OF THE FOLLOWING CRITERIA ARE MET: |
| 1.A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE, |
| ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT |
| ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON |
| DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER |
| TO THE SENSOR. |
| 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL |
| SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK |
| THE DOORS IN THE DIRECTION OF EGRESS. |
| 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE |
| DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE |
| LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND |
| WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS. |
| 4. THE MANUAL RELEASE DEVICE SHALL BE READILY |
| ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS |
| PUSH TO EXIT. |
| 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL |
| RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK, |
| INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS, |
| AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN |
| 30 SECONDS. |
| 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL |
| AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF |
| EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE |
| FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET. |
| 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER |
| SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL |
| AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF |
| EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE |
| FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET. |
| |
| SECTION 7.2.1.5.5 OF NFPA 101 FLORIDA EDITION 2009 |
| ALLOWS ELECTRICALLY CONTROLLED EGRESS DOOR ASSEMBLIES |
| IF EQUIPPED WITH APPROVED LISTED HARDWARE THAT |
| INCORPORATES A BUILT-IN SWITCH AND THE FOLLOWING FIVE |
| CRITERIA ARE MET: |
| 1. THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS |
| AFFIXED TO THE DOOR LEAF. |
| 2. THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION THAT |
| IS READILY OPERATED IN THE DIRECTION OF EGRESS. |
| 3. THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE |
| HAND IN THE DIRECTION OF EGRESS. |
| 4. OPERATION OF THE HARDWARE INTERRUPTS THE POWER |
| SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE |
| DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. |
| 5. LOSS OF POWER TO THE HARDWARE AUTOMATICALLY UNLOCKS |
| THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. |
| NOTE: THESE REQUIREMENTS ARE DIFFERENT THAN THE |
| REQUIREMENTS OF FOR MAGNETIC LOCKS WHEREBY AN OCCUPANT |
| SENSOR AND PUSH TO EXIT BUTTON ARE NEEDED IN ON THE |
| EGRESS SIDE. |
| |
| SHEET E2-1: NO EXIT SIGNAGE PROVIDED ON PLANS. |
| |
| SHEET FA0-1: PLANS INDICATE THE USE OF THE HORN-STROBE |
| DEVICES; VERIFY EXISTING FIRE ALARM SYSTEM IS NOT |
| EQUIPPED WITH SPEAKER-STROBE NOTIFICATION APPLIANCES. |
| |
| SHEET FA2-1: PROVIDE FIRE ALARM NOTIFICATION DEVICE IN |
| BATHROOMS #218 & #219. |
| |