Plan Review Notes
Plan Review Notes For Permit 12110304
Permit Number 12110304
Review Stop E
Sequence Number 1
Notes
Date Text
2012-11-13 08:34:51PLEASE PROVIDE MORE INFORMATION.
  
 SHOW LOCATION OF SERVICE, INCLUDE AN ELECTRICAL RISER
 PLAN WITH THE METER, GROUNDING , CONDUIT AND WIRE
 SIZES. INCLUDE LOCATION AND SIZE OF MAIN DISCONNECT.
 NEC 215.5
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
 561-805-6718