Plan Review Notes For Permit 12110274 |
Permit Number |
12110274 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-12-05 15:30:43 | FBC 2010 ACCESSIBILITY CODE | | FBC 2010 PLUMBING REVIEW #1 | | DENIED: | | | | 1. SHEET PTA-1 THE OCCUPANCY IS LISTED AS ASSEMBLY WITH | | 69 OCCUPANTS. SEPARATE FACILITIES ARE REQUIRED FOR MEN | | AND WOMEN. | | FBC PLUMBING 403.2 | | | | 2. SHEET PTA-1, SD-1.02: THE MENS ACCESSIBLE STALL WILL | | BE REQUIRED TO BE A MINIMUM OF 7'-1" WIDE TO ACHIEVE | | THE REQUIRED 5' CLEAR SPACE FOR THE WATER CLOSET | | FBC ACCESSIBILITY CODE 2010 604.3.1 A 60" CLEAR SPACE | | IS REQUIRED FOR WATER CLOSET FROM SIDE WALL. | | FBC ACCESSIBILITY CODE 2010 604.3.2 THE LAVATORY WILL | | NOT BE PERMITTED IN THE 60" SPACE. | | | | 3. SHEET PTA-1, SD-1.02: AN ACCESSIBLE WOMENS STALL | | WILL BE REQUIRED. | | FBC ACCESSIBILITY CODE 2010 213.3.1 | | | | 4. SHEET PTP-02 , SD-1.09 THE DRAINAGE CONNECTION FOR | | THE FILTER BACKWASH IS NOT SHOWN ON THE PTP-02 SANITARY | | DRAWING. THE BACKWASH WILL BE REQUIRED TO DRAIN TO THE | | SANITARY SYSTEM. | | CITY ORD. 90-203 | | | | 5. SHEET SD-1.05 (M) MAKE UP WATER SHALL BE PROTECTED | | FROM BACKFLOW. | | PLUMBING 608.3 | | | | 6. SHEET SD-1.10 THE AIR GAP DETAIL IS NOT A PROPER AIR | | GAP. THE DETAIL ALSO STATES THAT THE AIR GAP IS TO THE | | STORM SEWER. | | FBC 424.1.6.5.15 | | PLUMBING 202 AIR GAP (DRAINAGE SYSTEM). THE | | UNOBSTRUCTED VERTICAL DISTANCE THROUGH THE FREE | | ATMOSPHERE BETWEEN THE OUTLET OF THE WASTE PIPE AND THE | | FLOOD LEVEL RIM OF THE RECEPTACLE INTO WHICH THE WASTE | | PIPE IS DISCHARGING. | | | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|