2012-11-19 14:39:373401 PARKER AVENUE - RESTROOM & WATER FEATURE
 PERMIT #12110274
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO CIVIL DRAWINGS HAVE BEEN SUBMITTED FOR THE ENTIRE
 SITE SHOWING WATER MAINS, FIRE HYDRANT LOCATIONS, FIRE
 DEPARTMENT ACCESS ROADS, ETC.
  
 A FIRE DEPARTMENT ACCESS ROAD SHALL EXTEND TO WITHIN 50
 FEET OF AT LEAST ONE EXTERIOR DOOR THAT CAN BE OPENED
 FROM THE OUTSIDE AND THAT PROVIDES ACCESS TO THE
 INTERIOR OF THE BUILDING.
  
 PROVIDE A NAME, ADDRESS OR LETTER ON THE BUILDING SO
 THE LOCATION CAN BE IDENTIFIED BY EMERGENCY RESPONDERS.
 NUMBERS/LETTERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT
 WITH 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND.
  
 STRUCTURES WITH LIGHT FRAME ROOF TRUSS CONSTRUCTION
 SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO THE
 BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE LETTER R.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 INDICATE THE LOCATION OF THE NEAREST FIRE HYDRANT(S).
  