2012-12-05 13:56:22FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
  
 1. SHEET FHA-1: THE RESTROOMS WILL BE REQUIRED TO BE A
 MINIMUM OF 7'-1" WIDE TO ACHIEVE THE REQUIRED 60" CLEAR
 SPACE FOR THE WATER CLOSET ( OR THE LAVATORY COULD BE
 PLACED OUTSIDE OF THE 60" X 56" CLEAR SPACE).
 FBC ACCESSIBILITY CODE 2010 604.3.1 A 60" CLEAR SPACE
 IS REQUIRED FOR WATER CLOSET FROM SIDE WALL.
 FBC ACCESSIBILITY CODE 2010 604.3.2 THE LAVATORY WILL
 NOT BE PERMITTED IN THE 60" SPACE.
  