Plan Review Notes For Permit 12110273 |
Permit Number |
12110273 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-12-05 13:56:22 | FBC 2010 ACCESSIBILITY CODE | | FBC 2010 PLUMBING REVIEW #1 | | DENIED: | | | | | | 1. SHEET FHA-1: THE RESTROOMS WILL BE REQUIRED TO BE A | | MINIMUM OF 7'-1" WIDE TO ACHIEVE THE REQUIRED 60" CLEAR | | SPACE FOR THE WATER CLOSET ( OR THE LAVATORY COULD BE | | PLACED OUTSIDE OF THE 60" X 56" CLEAR SPACE). | | FBC ACCESSIBILITY CODE 2010 604.3.1 A 60" CLEAR SPACE | | IS REQUIRED FOR WATER CLOSET FROM SIDE WALL. | | FBC ACCESSIBILITY CODE 2010 604.3.2 THE LAVATORY WILL | | NOT BE PERMITTED IN THE 60" SPACE. | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|